Temporary installations for the continuity of overhead networks

Key benefits of CP solutions
Features
Thanks to their modular design, CP temporary solutions can be adapted to all common pylons without the need for anchoring, guaranteeing minimum space requirements.
Voltage levels
CP temporary devices are designed for voltage levels between 110 kV and 380 kV, guaranteeing broad compatibility with high-voltage overhead networks.
Quick assembly
The installation of a temporary CP system generally takes between 1 and 3 days, depending on the complexity of the conditions encountered on site.
Sustainable use
Although designed for temporary use, CP solutions can be implemented on a temporary or permanent basis, depending on the needs of the project.
Flexible integration of existing towers
The lower parts of CP solutions are designed to allow existing pylons to be taken over or new pylons to be installed, depending on project requirements.
Scope of services
Thanks to its emergency pylon solutions, CTEAM offers reliable and recognised solutions for various fields of application in the construction and operation of overhead lines
CP solutions in detail
CTEAM's CP solutions are available in several versions to meet the different requirements of overhead line construction. Each solution has specific features adapted to the constraints of the project.

CP-Light
Electrical circuits
2 x 110 kV
Wiring
Al/St 265/35 (264-AL1/34-ST1A)
Beam
Single cable
Average traction voltage
43 N/mm² of water
Phase amplitude
400 m
Deadweight coefficient
min/max 100 m/500 m
Wind/ice zone*/**
Wind zone 2 / Ice zone 2
CP
Electrical circuits
1x 380 kV
Wiring
Al/St 265/35 (264-AL1/34-ST1A)
Beam
4-conductor bundle
Average traction voltage
43 N/mm² of water
Phase amplitude
400 m
Deadweight coefficient
min/max 100 m/500 m
Wind/ice zone*/**
Wind zone 2 / Ice zone 2
CP-Heavy
Electrical circuits
2 x 380 kV
Wiring
Al/St 265/35 (264-AL1/34-ST1A)
Beam
4-conductor bundle
Average traction voltage
43 N/mm² of water
Phase amplitude
400 m
Deadweight coefficient
min/max 100 m/500 m
Wind/ice zone*/**
Wind zone 2 / Ice zone 2
CP lower section suitable for retrofitting existing pylons
Suitable for reusing existing pylons.
*Subject to compliance with the basic static dimensions, the CP solution can also be used with other cable sections or in areas subject to different wind and ice conditions.
**Full rated load capacity: no standard reduction in wind or ice loads is applied. However, specific adaptations can be defined according to project requirements.







Download our temporary solutions brochure in PDF format.